Current Diagnostics of Power Boiler System with Use of Fuzzy Logic

Jan Maciej Kościelny , Michał Syfert

Abstract

The paper presents diagnostics of power boiler system performed with use of the DIAG system. Fuzzy and neural local models of particular systems have been applied for fault detection. Obtained results of control valve and attemperator modelling have been presented. Fault isolation has been performed with use of the F-DTS method that bases on fuzzy appreciation of residuals and fuzzy reasoning. An example of fault isolation in a steam superheater and attemperator has been presented.
Author Jan Maciej Kościelny (FM / IACR)
Jan Maciej Kościelny,,
- The Institute of Automatic Control and Robotics
, Michał Syfert (FM / IACR)
Michał Syfert,,
- The Institute of Automatic Control and Robotics
Journal seriesIFAC Proceedings Volumes, ISSN 1474-6670
Issue year2000
Vol33
No11
Pages669-674
Publication size in sheets0.5
Conference4th IFAC Symposium on Fault Detection, Supervision and Safety for Technical Processes 2000 (SAFEPROCESS 2000), 14-06-2000 - 16-06-2000, Budapest, Węgry
Keywords in Englishfuzzy models, fuzzy inference, fault diagnosis, power system, diagnostic programs
DOIDOI:10.1016/S1474-6670(17)37437-2
URL https://www.sciencedirect.com/science/article/pii/S1474667017374372?via%3Dihub