Threats of contamination of drinking water by water from the fire protection systems

Agnieszka Malesińska , A. Czapczuk , J. Dawidowicz

Abstract

In accordance with applicable regulations, drinking water should be protected against secondary pollution. This is especially important when not only drinking water installations but also fire protection installations use one water supply. In the case of fire protection installations, the risk of water contamination is significant due to the higher pressure in the sprinkler systems. Adding right class backflow preventer to the water supply pipe will generate a significant loss of pressure. While in newly specified sprinkler systems additional pressure head may be taken into account at the calculation stage, it may be a problem in modernized existing installations.
Author Agnieszka Malesińska (FEE / DWSWT)
Agnieszka Malesińska,,
- Department of Water Supply and Wastewater Treatment
, A. Czapczuk
A. Czapczuk,,
-
, J. Dawidowicz
J. Dawidowicz,,
-
Pages163-166
Publication size in sheets0.5
Book Sobczuk Henryk, Kowalska Beata (eds.): Water Supply and Wastewater Disposal : Designing, Construction, Operation and Monitoring, 2020, ul. Nadbystrzycka 38C 20-618 Lublin, Wydawnictwo Politechniki Lubelskiej, ISBN 978-83-7947-409-7, 384 p.
Water Supply2020.pdf / No licence information (file archived - login or check accessibility on faculty)
Keywords in Englishsprinkler systems, secondary water contamination, backflow preventer, pressure loss
URL http://bc.pollub.pl/dlibra/publication/13786/edition/13459#description